太原市江阳化工厂职工医院 污水处理设施改造工程
技 术 方 案
太原美环工程设备有限公司
太原市江阳化工厂职工医院污水处理设施改造工程技术方案
目 录
一、总论 ················································································································ 2 二、设计依据 ·········································································································· 2 三、设计原则 ·········································································································· 3 四、设计水质及排放标准 ·························································································· 3 五、技术要求 ·········································································································· 4 六、生化池(生物接触氧化法)原理 ············································································· 5 七、技术方案 ·········································································································· 5 八、改造后工艺分析 ································································································ 7 九、投资估算 ·········································································································· 8 十、进度安排 ·········································································································· 9 十一、效益分析······································································································· 9 十二、售后服务······································································································· 9
太原市美环工程设备有限公司
1
太原市江阳化工厂职工医院污水处理设施改造工程技术方案
一、总论
1、项目名称及建设地点
项目名称:太原市江阳化工厂职工医院污水处理设施改造工程
建设地点:山西省太原市尖草坪区 2、工程概况
山西江阳化工厂地处太原市尖草坪区,工厂占地面积488万平方米,现有员工5000余人,坐落于厂区内的江阳医院是一个为所有职工提供医疗服务的机构。
随着医院的发展,医院原有的污水处理设施已不能满足医院发展的需要,根据医院总体规划,欲对原污水处理设施进行技术改造。我公司受江阳医院委托,在基本不改变已建成构筑物基础上对医院的污水处理设施改造工程进行技术改造方案设计.
二、设计依据
1、《医疗机构水污染物排放标准》(GB18466-2005) 2、《医院污水处理设计规范》(CECS07—88) 3、《室外排水设计规范》(GB50014-2006) 4、《环境工程手册》(水污染防治卷)
5、《全国统一安装工程预算定额山西省评估表》
6、《地下水池平面图》、《工艺流程图》(由甲方负责提供)
太原市美环工程设备有限公司
2
太原市江阳化工厂职工医院污水处理设施改造工程技术方案
三、设计原则
1、认真贯彻执行国家关于环境保护工作的方针和政策,使本工程设计符合国家有关法规、规范和标准。
2、根据环境及治理程度的要求,综合实际,考核比较各经济技术指标,优先采用低能耗、低运行费用、低基础建设费用、占地面积小、操作管理方便、稳定的处理工艺。
3、在基本不改变已建成构筑物的基础上,力求简捷,在满足达标排放的前提下,尽力降低改造费用。
4、新设备(更换陈旧、破损设备)及其辅助材料要经久耐用,操作、管理方便。
5、污水处理设备、器件的选用遵循质量第一、服务至上的原则。 6、污水处理工艺及设备采用自动化控制,操作简单,降低劳动强度,减少人工费用。
四、设计水质及排放标准
1、污水水质分析
医院污水水质类似于生活污水,但成份复杂。如消毒剂,来自化验、检验、手术等各科室的重金属、有机试剂,以及可能的放射性同位素等。做为医院,其排放的污水中含有大量有毒化学物质和多种致病菌、病毒和寄生虫卵,它们在环境中具有一定的适应能力,有的甚至在污水中存活时间较长,若未处理或处理不当即排入水体或用于灌溉,将会污染环境、影响人们的身体健康。 2、出水水质指标
太原市美环工程设备有限公司
3
太原市江阳化工厂职工医院污水处理设施改造工程技术方案
根据2003年12月国家环保总局《医院污水处理技术指南》环发(2003)197号的精神,参考国家环保部门要求,治理后达到《医疗机构水污染排放标准》GB18466-2005中预处理排放标准。具体指标如下:
排放标准项目 值 粪大肠菌群数 肠道致病菌 肠道病毒 PH值 COD BOD 悬浮物 氨氮 动植物油 石油类 阴离子表面活性11 剂 24 总余氯 — 10mg/L 23 总β 10 Bq/L 5000MPN/L 不得检出 不得检出 6~9 250mg/L 100mg/L 60mg/L — 20mg/L 20mg/L 13 14 15 16 17 18 19 20 21 22 12 数) 挥发酚 总氰化物 总汞 总镉 总铬 六价铬 总砷 总铅 总银 总α 1。0mg/L 0。5mg/L 0.05mg/L 0.1 mg/L 1.5 mg/L 0.5 mg/L 0。5mg/L 1.0 mg/L 0.5 mg/L 1Bq/L 色度(稀释倍— 序号 1 2 3 4 5 6 7 8 9 10 五、技术要求
由于一级处理不能达到现行排放标准,需要通过增加生化池以及对陈旧设备的维护与更新,确保污水达标排放。
太原市美环工程设备有限公司
4
太原市江阳化工厂职工医院污水处理设施改造工程技术方案
六、生化池(生物接触氧化法)原理
生化池即生物接触氧化池,其在反应池内设置填料,经过充氧(曝气机)的废水与长满生物膜的填料相接触,在生物膜的作用下,废水得到净化。生物接触氧化法在运行初期,少量的细菌附着于填料表面,由于细菌的繁殖逐渐形成很薄的生物膜。在溶解氧和食物都充足的条件下,微生物的繁殖十分迅速,生物膜逐渐增厚.溶解氧和污水中的有机物凭借扩散作用,为微生物所利用。但当生物膜达到一定厚度时,氧已经无法向生物膜内层扩散,好氧菌死亡,而兼性细菌、厌氧菌在内层开始反之,形成厌氧层,利用死亡的好氧菌为基质,并在此基础上不断发展厌氧菌。经过一段时间后在数量上开始下降,加上代谢气体产物的逸出,使内层生物膜大量脱落。在生物膜已脱落的填料表面上,新的生物膜又重新发展起来.在接触氧化池内,由于填料表面积较大,所以生物膜发展的每一个阶段都是同时存在的,使去除有机物的能力稳定在一定的水平上.生物膜在池内呈立体结构,对保持稳定的处理能力有利。
其特点是在池内设置填料,池底曝气对污水进行充氧,并使池体内污水处于流动状态,以保证污水与污水中的填料充分接触,避免生物接触氧化池中存在污水与填料接触不均的缺陷。
七、技术方案
经过研究,我公司主要进行如下技术改造: 1、处理原池体
由于长时间的污水处理导致池体污泥堆积.所以,首先对各污水池进
太原市美环工程设备有限公司
5
太原市江阳化工厂职工医院污水处理设施改造工程技术方案
行清理、冲洗等,将淤积的污泥污水进行清除、清理。 2、维修操作间
操作间的门窗陈旧破损,故将其均改造为较为结实的塑钢结构;同时对室内墙体进行抹灰处理。 3、更换电控柜
由于长期使用,导致原有的电控柜陈旧破损,需更换一套全新的自动化电控柜,包括絮凝、消毒等加药设备. 4、新建生化池
采用原先预留的池子作为生化池,池内所需设备如下: (1)做填料支架。 (2)填料选型
选用载体填料必须考虑生物膜的附着性、填料的化学稳定性、比表面积、强度、空隙率等参数指标要好。
填料的形式有多种,目前国内常用的有:蜂窝管式填料、软性填料、半软性填料、弹性立体填料等,其中蜂窝管式填料容易堵塞,软性纤维填料易于粘合,而弹性立体填料相对于其它填料有使用寿命长、充氧性能好、启动挂摸快、脱膜更新容易、耐高负荷冲击、处理效果显著、运行管理简便、不堵塞、不结团和价格低廉等优点,本生化池填料采用弹性立体填料。 (3)曝气装置
目前,曝气充氧设备采用穿孔管、曝气头、水下曝气机、曝气器和变孔曝气软管等。
我公司建议采用水下曝气机,具体分析如下:
太原市美环工程设备有限公司
6
太原市江阳化工厂职工医院污水处理设施改造工程技术方案
优点:由于其不需设风机,投资少,运行成本小等优点,并且克服了曝气机噪声大、占地面积大、管理布置复杂等缺点;而且以后的清掏也更为方便。
八、改造后工艺分析
参照《医院污水处理设计规范》CECS 07:2004国家标准规定进行工程设计改造,通过增加二级生化处理,有效的去除有机污染。该处理工艺已在实际中长期使用,工艺比较成熟。工艺图如下:
格 调生消医院 达标 节化毒污水 排放
栅 池 池 池 废水处理系统工艺流程框图
从流程图可看出,医院排污口排出的污水经化粪池腐化沉淀,由格栅去除大颗粒状和纤维状杂质后,自流进入调节池,在池内对水质、水量进行调节、中和;由泵提升流入接触氧化池进行生化处理,接触氧化池内投放高效微生物,在水池底部安装离心式曝气机,以供微生物生存和繁殖,从而更好的处理污水中的有机物,使水质得到净化;污水经生化处理去除有机污染物后流入消毒池,与次氯酸钠消毒剂混合消毒,最终达标排放。
太原市美环工程设备有限公司
7
太原市江阳化工厂职工医院污水处理设施改造工程技术方案
九、投资估算
投资估算表
序名称 号 土建 1 部塑钢门窗 分 Φ16圆钢和填料支架 50角铁制作 设备 2 部分 电控柜 曝气机 絮凝剂加药装置 消毒剂加药装置 3 4 5 检测费 其他费用 合计 1台 1台 1套 1套 待定 8
单价数量 (元) 清掏 抹灰 140 m² 16m² 总价备注 (元) 所有池体 立体弹性 生物填料 Φ150,间距100 QXB2.5KW 公司自研 公司自研 太原市美环工程设备有限公司
太原市江阳化工厂职工医院污水处理设施改造工程技术方案
十、进度安排
序号 1 2 3 4 5 6 7 项目内容 技术方案编制 施工图设计 土建项目施工 设备制造及安装 管道安装 调试及试运转 项目验收 日期 5天 备注 十一、效益分析
1、本项目充分利用现有设备和构筑物,通过选用高效、先进水处理设备,装置占地少、运行费用低,经济效益较好。
2、本项目的实施,可确保医院废水污染物稳定达标排放,降低对周围环境的影响,环境效益明显。
3、项目实施后,由于污染物实现达标排放,为同类废水的治理树立一个样板工程,社会效益相当明显。
十二、售后服务
本公司免费为医院提供技术咨询,根据其要求提供方案设计;积极与医院配合,按期出好施工图。
施工期间本公司将派专业人员在现场进行监督及配合,保证工程进度
太原市美环工程设备有限公司
9
太原市江阳化工厂职工医院污水处理设施改造工程技术方案
及质量。
安装调试期间免费为用户代培操作工,到单独熟练操作为止,免费为用户提供有关操作规程及规章制度。
按设计标准及设计参数对设备及处理指标进行验收考核,达不到标准由本公司负责整改,直到达标为止。
设备在通过验收考核交付使用后,在质保期内,属于医院设备质量问题出现故障,在接到医院书面或者电话通知后我公司在8小时内派人到现场进行维修等售后服务,以保证机组正常运行。
设备免费保修一年,终身维修,在保修期内设备发生故障及时赶赴现场排除,保修期满,本公司定期或不定期每年二次走访医院,维修、检查、指导,发现问题随时解决。
太原市美环工程设备有限公司
二O一一年四月二十六日
太原市美环工程设备有限公司
10
因篇幅问题不能全部显示,请点此查看更多更全内容